The number of loops decides which manifold to buy and whether the floor heats evenly. A loop that is too long cannot be pumped properly and its far end stays cold; too many short loops mean paying for a bigger manifold and extra work. The calculation is simple once you know three figures.

What the diagram shows

1 — the manifold, 2 — serpentine layout, 3 — spiral layout, 4 — pipe spacing (the distance between neighbouring pipes).

Three figures for the calculation

  • Length of one loop: up to 80–100 m for 16 mm pipe (preferably no more than 80), up to 120 m for 20 mm. The length includes the leads from the manifold to the room.
  • Pipe per 1 m²: 10 cm spacing — about 10 m, 15 cm — about 6.7 m, 20 cm — about 5 m.
  • Length difference between loops on one manifold — ideally no more than 15–20 %, otherwise they cannot be balanced without flow meters.

So one 16 mm loop at 15 cm spacing covers 80 m ÷ 6.7 m ≈ 12 m². That is where the rule “one loop per 10–15 m² of floor” comes from.

Counting loops

  1. Subtract areas under kitchen units, wardrobes and the bath from each room — the floor is not heated there.
  2. Choose the spacing: 15 cm for living rooms, 10 cm by panoramic windows and in bathrooms, 20 cm in a well-insulated house.
  3. Give every room at least its own loop so its temperature can be controlled separately. Split a large room into 2–3 loops of roughly equal length.
  4. Add up the loops — that is the number of manifold outlets.
Example: a 60 m² flat with a 20 m² living room, 14 m² bedroom, 10 m² kitchen and 5 m² bathroom. The living room gets 2 loops, the rest one each: 5 loops in total, so a 5-outlet manifold.

Serpentine or spiral

A serpentine (2) is easier to lay, but the water cools along the loop, so the floor is warmer at the start than at the end; it is used in small rooms and along cold walls. A spiral (3) alternates flow and return side by side, so it heats the floor evenly and bends the pipe less sharply — it is the main layout for living rooms.

Choose the manifold by the number of loops: selections for 3, 4, 5 and 6 loops and all underfloor heating manifolds; add a cabinet and PEX-a pipe. How to build the whole assembly — see “Water underfloor heating: layout”.